Petbow Cummins NT855 Series Diesel Generator

Petbow Cummins Diesel GeneratorPetbow Cummins Generators 312 to 390 kVA

Petbow Generating Sets Powered By Cummins Diesel Engines

Circuit Breaker Cubicle
3-pole moulded case circuit breaker with optional shunt trip and auxiliary contacts.

Finish
High gloss green finish.

General
Set of operating and instruction manuals.

Options
Refer distributor for range details.

Panel Standard Specification

  • Run-stop-remote switch.
  • Automatic remote starting, 2 wire.
  • Coolant temperature gauge.
  • Oil pressure gauge.
  • DC voltmeter.
  • Running time meter.
  • Fault reset switch.
  • Lamp test switch.
  • AC voltmeter / ammeter with selector switch.
  • Dual scale frequency meter / tachometer.
  • Emergency stop.
  • Engine monitoring and shutdown for:
    • low oil pressure
    • high coolant temperature
    • over crank
    • over speed
    • low coolant level
  • Common external alarms

Optional MONZA Acoustic Enclosure

  • 70 dBA @ 7 metres (average).
  • 4 point lift and skid ends standard.
  • Central lifting frame optional.
  • Lockable doors.
  • Vertical air discharge.
  • Compact footprint design.

Optional CONTRACTOR Acoustic Enclosure

  • 85 dBA @ 1 metre (average).
  • 4 point lift and skid ends standard.
  • Central lifting frame optional.
  • Extended fuel tank option (with skid ends).
  • Vertical air discharge.
  • Locable doors.

12 Lite Detector Control Panel

  • Controls generator set start and shutdown.
  • Automatic remote start.
  • DC panel lighting.
  • Panel mounted on vibration isolators.
  • Analog gauges display performance trends.

Engine

Cummins NT/A855, 6 cylinder, diesel engines. 50°C radiator. 24 Volt starting, battery charge alternator. Spin-on replaceable element fuel and oil filters. Electronic governor. Dry element air filter.

Alternator

Brushless, single bearing, revolving field. 4-pole screen protected drip proof. Class H insulation. Rotor and exciter impregnated with tropical grad insulating polyester resin. Epoxy coated stator winding. Sealed solid state automatic voltage regulator. Permanent magnet exciter.

Chassis

Fabricated and welded chassis. Builtin anti-vibration mountings. In-skid fuel tank. Flexible fuel lines.

Technical Data Generating Sets
Set model BM-250A CB-280A
Prime rating* 250kWe 312kVA 280kWe 350kVA
Standby rating" 275kWe 343kVA 312kWe 390kVA
Set output 380/415V 50 Hz 380/415V 50 Hz
Engine make Cummins Cummins
Model NT855G6 NTA855G4
Cylinders Six Six
Engine configuration In-line In-line
Governor / class Electronic Electronic
Aspiration Turbocharged Turbocharged Aftercooled
Bore and stroke 140mm x 152mm 140mm x 152mm
Compression ratio 14:1 14:1
Cubic capacity 14 Litres 14 Litres
Cranking current @ 0°c 640A 640A
Engine Output-Prime 272 kWm 309 kWm
Nett at flywheel- standby 302 kWm 342 kWm
Max. load acceptance - single steps 172 kWe 175 kWe
Alternator size (Prime) HC434E HC434F
Alternator voltage regulation ±1.0% ±1.0%
Alternator insulation class H H
Fuel consumption (Prime) 100% load 69 L/hr 76 L/hr
Fuel consumption (Standby) 100% load 76 L/hr 84 L/hr
Lubrication oil consumption 0.5% of fuel consumption 0.5% of fuel consumption
Lubrication oil capacity 38.6 Litres 38.6 Litres
In-skid fuel tank capacity-open set 600 Litres 600 Litres
Fuel tank capacity - MONZA Canopy 1300 Litres 1300 Litres
Fuel tank capacity - CONTRACTOR Canopy 850 Litres 850 Litres
Ext. fuel tank capacity - CONTRACTOR Canopy 1300 Litres 1300 Litres
Coolant capacity-radiator and engine 69.3 Litres 69.8 Litres
Exhaust temp-full load 574°C 524°C
Exhaust gas flow-full load prime 1.071 m3/s, 3855.6M3/hr 1.128M3/s, 4060.8M3/hr
Exhaust gas back pressure max 10.2 kPa, 76mm Hg 10.2 kPa, 76mm Hg
Air flow-radiator (50°C ambient) 8.6M3/s, 30960M3/hr 8.6 m3/s, 30960m3/hr
Air flow - engine intake 0.3608m3/s, 1299M3/hr 0.408m3/s, 1468.8M3/hr
Heat radiated to ambient 57 kW 65 kW
Derating factors - temp. 2% per 11 °C above 40°C 2% per 11 °C above 40°C
Derating factors - altitude 4% per 300m above 1525m 4% per 300 m above 1525m